(Created page with "This section controls various configuration settings for A/D, P/R and Hardware acceleration. ===Acquisition=== thumb ;Try to use Fast Downloading :If checked, the data download from the A/D will start immediately when the board is armed. If the data download rate is low, this may cause DMA timeout errors. ;Disable Burst DMA :This option is set at the factory and should not be change...") |
No edit summary |
||
| Line 3: | Line 3: | ||
===Acquisition=== | ===Acquisition=== | ||
[[File:ConfigurationInstrumentsAD.png|thumb]] | [[File:ConfigurationInstrumentsAD.png|thumb]] | ||
====Try to use Fast Downloading==== | |||
If checked, the data download from the A/D will start immediately when the board is armed. If the data download rate is low, this may cause DMA timeout errors. | |||
====Disable Burst DMA==== | |||
This option is set at the factory and should not be changed. | |||
====Discard Follower Data==== | |||
If checked the preliminary TOF image will be discarded. | |||
====Disable Advanced Follower features==== | |||
If checked, Follower gates will collect TOF data only. | |||
====Match Thickness Type on Parent==== | |||
If checked, the Thickness type being collected will be matched on the parent Follower (e.g. Peak-to-Peak, Edge-to-Edge, etc), rather than always using the Edge crossing. This will be disabled if the ====Disable Advanced Follower Features" option is checked.==== | |||
Ignore Peak Thresholds | |||
If checked peak amplitude data will be collected regardless of threshold size. Rising/Falling edge TOF is not valid while this checkbox is checked. | |||
====Enable Gate Gains==== | |||
If checked, the user can adjust the gain on the waveform within a gate region. | |||
====Always use Software Trigger when not scanning==== | |||
If checked, the digital oscilloscopes will always be triggered by ODIS when not in a scan, at a rate of approximately 20 times a second (this will vary depending on scope and gate settings). The trigger setting for the board is ignored until the scan starts. Whether or not a board actually triggers depends on if it is enabled and if appropriate trigger connections and pulser/receiver settings are present. | |||
====Allow different trigger modes per channel==== | |||
If checked, the default trigger mode can be overridden by selecting the trigger modes via the [[Digital Oscilloscope]]. | |||
====Don't trigger on channels that are not visible==== | |||
If checked, only the currently visible Scope tab will update when idle. Other channels will not be triggered. | |||
====A/D Encoder resolutions==== | |||
This sets the counts per physical unit that the A/D board(s) use to to calculate increments when using [[Triggering#Pulse-On-Position (Encoder Triggering)|Encoder Triggering]]. | |||
===P/R=== | ===P/R=== | ||
Revision as of 14:56, 14 May 2025
This section controls various configuration settings for A/D, P/R and Hardware acceleration.
Acquisition
Try to use Fast Downloading
If checked, the data download from the A/D will start immediately when the board is armed. If the data download rate is low, this may cause DMA timeout errors.
Disable Burst DMA
This option is set at the factory and should not be changed.
Discard Follower Data
If checked the preliminary TOF image will be discarded.
Disable Advanced Follower features
If checked, Follower gates will collect TOF data only.
Match Thickness Type on Parent
If checked, the Thickness type being collected will be matched on the parent Follower (e.g. Peak-to-Peak, Edge-to-Edge, etc), rather than always using the Edge crossing. This will be disabled if the ====Disable Advanced Follower Features" option is checked.==== Ignore Peak Thresholds If checked peak amplitude data will be collected regardless of threshold size. Rising/Falling edge TOF is not valid while this checkbox is checked.
Enable Gate Gains
If checked, the user can adjust the gain on the waveform within a gate region.
Always use Software Trigger when not scanning
If checked, the digital oscilloscopes will always be triggered by ODIS when not in a scan, at a rate of approximately 20 times a second (this will vary depending on scope and gate settings). The trigger setting for the board is ignored until the scan starts. Whether or not a board actually triggers depends on if it is enabled and if appropriate trigger connections and pulser/receiver settings are present.
Allow different trigger modes per channel
If checked, the default trigger mode can be overridden by selecting the trigger modes via the Digital Oscilloscope.
Don't trigger on channels that are not visible
If checked, only the currently visible Scope tab will update when idle. Other channels will not be triggered.
A/D Encoder resolutions
This sets the counts per physical unit that the A/D board(s) use to to calculate increments when using Encoder Triggering.
P/R
- If Idle, Disable P/Rs
- This option can be used to turn off the P/R(s) after a certain time has passed without any activity detected. This helps prevent long-term wear on the pulser and transducers. Set to "Never" to keep the pulser on at all times. If a scan is running, this parameter is ignored.
- Clamp Pulser Energy
- This is a factory setting and should not be changed.